Applications: ideal for high and large space (H: 4-30m) that needs heating with max 23m supply air height.
Model: AirTS-DM-I, AirTS-DM-II
Function: heating
Hot source: hot water (40-90℃) /steam (<120℃)
Control mode: wireless control, variable frequency, auto monitoring
Quality Assurance
Stable and Durable.
After-sales Service
24H Online.
Working Principle
When hot water or steam passes the equipment, the efficient heat exchanger in the equipment is used to achieve rapid heating of the air.
The large wind pressure axial flow fan installed on the top is used to forcedly press the hot air down. Then the air is subject to pressure boost twice through the silencer sponge and the lower trapezoidal convergence, swirls out from the nozzle through the guide vane and is distributed throughout the space from top to down.
Functions
Fall prevention warning monitoring
Working data collection and analysis
Variable air volume and water volume
Wireless intelligent control
Filter net self-cleaning
Function: heating
Support full linkage control
Light breeze air supply
Technical Comparison
AirTS top heating unit
High and large space air conditioner lifted on the roof
It achieves heating air from the air exchanger in the equipment
It distributes the hot air by means of efficient air distributor, which eliminate the undesirable indoor temp layers
Comfortable heating environment without wind feeling sense
Bottom heating unit
In high large space with great depth, using radiator can allow natural air convection as hot air rises
It can only radiate into small area with the range less than 5m. The heat rising to the roof will be dissipated and the temp cannot be achieved effectively in the middle area.
Radiator heating requires high requirements for supply water temp.
AirTS units temp field
Our heating units forcedly and quickly send the hot air down, make the temp in the working area rise rapidly.
Radiator heating temp field
It can be seen from the radiator heating temp field image that the heat is mainly gathered on the roof and the temp is low in the lower working area.
Specification
Louvered Recirculated Air Heating Unit | |||
Model | AirTS-DM-I | AirTS-DM-II | |
Rotating speed of fan | r/min | 0~1300 | 0~860 |
Standard circulating air volume | m³/h | 0~5500 | 0~10500 |
Voltage | V | 380±5% | 380±5% |
Electric power | kW | 0~0.85 | 0~1.80 |
Current | A | 0~1.65 | 0~3.60 |
Suitable installation height | m | 4~8 | 4~17 |
Control mode | VAV stepless regulation | VAV stepless regulation | |
Noise | dB | <59 | <65 |
Dimension | |||
Model | AirTS-DM-I | AirTS-DM-II | |
A | mm | 710 | 1110 |
B | mm | 600 | 800 |
C | mm | 492 | 850 |
E | mm | 175 | 150 |
F | mm | 100 | 100 |
J | mm | 467 | 320 |
K | mm | 418 | 240 |
N (internal thread) | mm | DN25 | DN40 |
Weight | kg | 85 | 125 |
Water volume | L | 4.35 | 9.8 |